Huawei FusionModule2000 Product Description page 40

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Category
Battery
System
Others
Issue 04 (2017-06-30)
Item
Number of batteries
Battery string sharing
Charging voltage
Display
System efficiency
Current equalization
Number of parallel
cabinets
Cable connection
Rated power
Noise
Maintenance mode
Surge protection
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
125% < load ≤ 150%: transfer to bypass
mode after 1 min
Bypass overload capability:
Load ≤ 135%: run continuously at 30°C or
lower
Load ≤ 125%: run continuously at 40° C or
lower
1000% load: run for 100 ms
30 to 40 12 V batteries (32 batteries by default)
Derated by 6% when 30 batteries are used
Batteries are shared in the rack by default.
Cabinets are not connected in parallel inside
the smart module.
Equalized charging voltage: 2.35 V/cell; float
charging voltage: 2.25 V/cell
The maximum battery capacity is 3000 Ah.
The charging current is limited based on the
battery capacity.
LCD+LED
96%
< 5% (in parallel mode)
Cabinets do not need to be connected in
parallel inside the smart module.
Routed in and out from the top
The integrated UPS cabinet supports the 3+1
working mode (three power modules and one
redundant module) and supports up to 112 kW
IT equipment. IT cabinet power can be 32 kW
(1+1), 72 kW (2+1), or 112 kW (3+1).
At atmospheric pressure (25° C)
25% load: 54 dB
50% load: 58 dB
75% load: 61 dB
100% load: 65 dB
Maintained from the front or rear
Level C surge protective device (SPD)
3 System Architecture
33