Huawei FusionModule2000 Product Description page 130

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Item
RS485 or
control area
network
(CAN)
PoE port
BLINK
button
E-label
Indicators
Table 3-90 describes the indicators on the ETH converter.
Table 3-90 ETH converter indicators
Indicator
PWR
RUN
ALM
Issue 04 (2017-06-30)
Specifications
PoE input: 36–60 V DC power input
Provides two RS485/CAN ports. The default communications rate for the
RS485 port is 9600 bit/s, and that for the CAN port is 125 kbit/s. Both
ports match the RJ45 terminal shared by RS485 and CAN.
Provides one PoE port with the communications rate of 10/100M.
If you press the BLINK button, the RUN indicator blinks intermittently at
super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 10 seconds.
Supported
Color
Name
Green
Power input
status
indicator
Green
Operating
status
indicator
Red
Alarm
indicator
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The ETH converter
long intervals
successfully registers with the
ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The communication fails or
short
the ETH converter fails to
intervals
register with the ECC800 (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
3 System Architecture