Huawei FusionModule2000 Product Description page 96

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Indicator
RUN
ALM
3G
RF_Z
Issue 04 (2017-06-30)
Color
Name
Green
Running status
indicator
Red
Alarm indicator
Green
3G status
indicator
Green
Communication
status indicator
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
Status
Description
Steady on
The power supply is normal,
the program is being loaded,
or WiFi WPS is pairing.
Off
The power supply is
abnormal.
Blinking at
The software runs properly
long
(the indicator blinks at 0.5
intervals
Hz, on for 1s and then off
for 1s) or the ECC800
registers with the NetEco
successfully.
Blinking at
The ECC800 does not
short
register with the NetEco (the
intervals
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Steady on
A system failure alarm is
generated.
Off
The system is normal.
Steady on
The 3G module is powered
on.
Off
The 3G module stops
running, or no 3G module is
configured.
Blinking at
The 3G module succeeds in
long
dial-up (the indicator blinks
intervals
at 0.5 Hz, on for 1s and then
off for 1s).
Blinking at
The 3G module registers
short
with the operator network
intervals
successfully (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
Steady on
No network parameters
exist, or a network is to be
created.
Blinking at
A network is set up, and no
long
node access is allowed (the
intervals
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
A network is set up, and
super short
node access is allowed (the
intervals
indicator blinks at 10 Hz, on
for 0.05s and then off for
89

Advertisement

Table of Contents
loading

Table of Contents