FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Integration
Security and Reliability
Space Saving and Energy Efficiency
Quick Installation
Optimal Compatibility
Issue 04 (2017-06-30)
The smart module integrates a cabinet system, power supply and distribution system,
cooling system, facility management system, surge protection and grounding system,
auxiliary fire extinguishing system, and integrated cabling system. It provides an overall
solution.
The integrated power supply and distribution system has an automatic transfer switch
(ATS), and distributes power to uninterruptible power systems (UPSs), air conditioners,
and IT equipment.
When the 380 V power supply is used and there are more than four battery cabinets or when the 480 V
power supply is used, battery racks are independently deployed.
The smart module supports optional aisle and cabinet access control, which prevents
unauthorized personnel from entering the smart module and improves security.
The auxiliary fire extinguishing system improves the data center safety. It consists of the
rotating skylight which opens automatically in case of fire and the emergency button
which helps open the door in case of emergency.
The smart module supports two power inputs.
Each UPS is configured with a manual maintenance bypass switch. When the smart
module is working properly, the switch is turned off to prevent misoperations.
Modular UPSs work in N+1 redundancy mode to improve the reliability of the smart
module.
Strong current and weak current cables, optical fibers, and network cables are routed
separately to minimize electromagnetic interference.
The electronic expansion valve used in an air conditioner has a backup power module
which ensures that the electronic expansion valve can be closed when the system is
powered off, thereby preventing compressor damage.
The positive temperature coefficient (PTC) electric heater of the air conditioner provides
dual protection functions: automatic reset and auto-recovery disabling.
The smart module can be placed in a room of an office building.
The smart module can be directly installed on a concrete floor in a building, which
simplifies engineering.
Equipment room area ≤ 300 m
Aisle lighting is available, saving electric energy.
The smart module is delivered within a few days and can be quickly installed onsite.
The design minimizes the workload of engineering.
The standardized installation procedures reduce the installation time and workload.
T1 environments are supported.
Modular power distribution allows for smooth expansion to meet various requirements.