Technical Specifications - Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
If the inlet water contains large granules, install a water filtering device at the inlet port to
prevent pipe blockage.
Table 3-42 describes the NetCol5000-A water quality requirements.
Table 3-42 Water quality requirements
Name
Hydrogen ion
Conductivity at 20ºC (σ
a: If σ
for the first time. If σ

3.3.4.3 Technical Specifications

Table 3-43 and Table 3-44 respectively list the main technical specifications of the
NetCol5000-A in-row precision air conditioner.
Table 3-43 Generic specifications
Item
Power supply
Voltage tolerance
Frequency tolerance
Cooling mode
Refrigerant
Cooling capacity
Air supply mode
Rated air volume
Air filter level
Standard dimensions (H x W x D)
a: By using an optional voltage jumper, the air conditioner is compatible with the following
power systems: 380 V AC 50/60 Hz 3W+PE, 400 V AC 50/60 Hz 3W+PE, 415 V AC
50/60 Hz 3W+PE, 440 V AC 60 Hz 3W+PE, 460 V AC 60 Hz 3W+PE, and 480 V AC 60
Hz 3W+PE.
b: If the upstream voltage may fluctuate outside the voltage tolerance, install a voltage
stabilizer; otherwise, the air conditioner may fail to run properly due to frequent alarms.
c: The specifications apply to rated working conditions (indoor dry-bulb temperature:
Issue 04 (2017-06-30)
a
)
20
is less than 300 μS/cm, it takes a longer time for the humidifier to generate vapor
20
is greater than 1250 μS/cm, the humidifier service life is affected.
20
a
b
c
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Requirements
7–8.5
300–1250
NetCol5000-A
380–480 V AC 50/60 Hz 3W+PE
Rated voltage± 10%
Rated frequency± 3 Hz
Air cooled
R410A
35 kW
Horizontal flow
3
6800 m
G4
d
2000 mm x 600 mm x 1100 mm
3 System Architecture
Unit
pH
µ S/cm
/h
71

Advertisement

Table of Contents
loading