Technical Specifications; Management System; Overview - Huawei FusionModule500 Smart User Manual

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Table 3-7 Derating coefficients
Altitude
(m)
Air
volume
coefficie
nt
Cooling
capacity
coefficie
nt

3.3.2 Technical Specifications

Table 3-8 Technical specifications
Item
Power system
Refrigerant
Cooling capacity
Air supply mode
Dimensions (H x W x D)
Net weight
IP rating
a: The cooling capacity is obtained when the cabinet internal dry bulb
temperature is 37°C, the cabinet internal wet bulb temperature is 24°C, and the
cabinet external dry bulb temperature is 35°C. The actual cooling capacity varies
depending on the ambient temperatures and relative humidity inside and
outside the cabinet.

3.4 Management System

3.4.1 Overview

The smart module monitoring solution consists of the collector and monitoring
components. The ECC800-Pro functions as the collector.
The smart module provides a module-level pad for local intelligent management
in terms of real-time monitoring, status browsing, alarm management, and
system configuration.
Issue 02 (2021-06-30)
0
1000
1500
1
0.887
0.835
1
0.940
0.909
Integrated Air Conditioner
208–240 V AC, 50/60 Hz, 1 Ph
R410A
3.5 kW
Front flow or front upflow
355 mm x 442 mm x 930 mm
b
≤ 60 kg
IP20
Copyright © Huawei Technologies Co., Ltd.
2000
2500
3000
0.785
0.737
0.692
0.878
0.846
0.815
a
3 System Architecture
3500
4000
0.649
0.608
0.784
0.753
25