6.1.2 Quarterly Maintenance

Table 6-2 Quarterly preventive maintenance table
Maintenance
Area
Power supply and
distribution
system
UPS
Issue 02 (2021-06-30)
Maintenance
Operation
Item
Operating status
Check the surge
of the surge
protection
protection module
module indicator
and MCB status.
Operating
-
environment
LCD
-
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshootin
g
● The surge
● If the surge
protection
module
indicator is
steady green.
● The MCB is
switched on.
● If the MCB is
● Ambient
● If the
temperature:
0°C to 40°C
● Humidity:
0%–95% RH
(non-
condensing)
● If the input
According to the
If an alarm is
status icons on
present, rectify
the LCD, all units
the fault by
are operating
checking the
properly. No
device status
fault or alarm
and parameters.
information is
found in the
active and
historical alarm
records.
6 O&M
protection
module
indicator is
red, replace
the surge
protection
module.
off, switch it
on.
temperature
or humidity
is abnormal,
check the
smart
cooling
product
status.
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
154