6.2.1 Power Supply and Distribution System Troubleshooting

Except mains outage, power supply and distribution faults are caused by the
damage or failure of one or more components. Rectify the faults based on fault
location and fault type.
● When a UPS is faulty, alarm information is displayed on the LCD. Critical alarms
must be handled before powering on the UPS again. Otherwise, the fault may
be extended, or the UPS may be damaged.
● If the fault is not rectified, contact Huawei technical support.
Table 6-4 Power supply and distribution system troubleshooting
Symptom
The power input to the
downstream device is
abnormal.
Issue 02 (2021-06-30)
Maintenance
Item
Functions of the
water sensor and
water detection
cable
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Operation
Expected Result
Place the water
A water leakage
detection cable
alarm is
into the water
generated.
and check
whether a water
leakage alarm is
generated by the
water sensor.
Possible Cause
● The switch trips
abnormally.
● The UPS is faulty.
6 O&M
Troubleshootin
g
If a water
leakage alarm is
not generated,
replace the
water detection
cable.
Measure
● Use a multimeter to
check whether there
is a short circuit. Turn
on the switch again,
and check whether
the system is
overloaded.
● Restart the UPS. If the
UPS is faulty, replace
it.