Yearly Maintenance - Huawei FusionModule500 Smart User Manual

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Maintenance
Area
Water sensor and
water detection
cable

6.1.3 Yearly Maintenance

Table 6-3 Yearly preventive maintenance table
Maintenance
Area
Power supply and
distribution
system
Issue 02 (2021-06-30)
Maintenance
Operation
Item
Functions of the
Place the water
water sensor and
detection cable
water detection
into the water
cable
and check
whether a water
leakage alarm is
generated by the
water sensor.
Maintenance
Operation
Item
Operating status
Check the surge
of the surge
protection
protection module
module indicator
and MCB status.
Dust inside the
Check whether
power distribution
there is dust on
subrack
the power
distribution
subrack panel.
Bolts between
Tighten all bolts
power cables and
regularly using an
the busbar
adjustable
wrench after
powering off the
device.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshootin
g
A water leakage
If a water
alarm is
leakage alarm is
generated.
not generated,
replace the
water detection
cable.
Expected Result
Troubleshootin
g
● The surge
● If the surge
protection
module
indicator is
steady green.
● The MCB is
switched on.
● If the MCB is
The white paper
If the white
that you use to
paper is dirty,
wipe the PDC
clean the power
panels is clean.
distribution
subrack.
The bolts are
Tighten a bolt if
secured.
it is loose.
6 O&M
protection
module
indicator is
red, replace
the surge
protection
module.
off, switch it
on.
161

Advertisement

Table of Contents
loading

Table of Contents