Huawei FusionModule500 Smart User Manual page 165

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Maintenance
Area
Issue 02 (2021-06-30)
Maintenance
Operation
Item
Battery
-
appearance
Battery operating
-
temperature
Battery
-
management
parameter settings
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshootin
g
1. The surface is
If the battery
clean and tidy
appearance is
without
abnormal,
stains.
contact Huawei
technical
2. The battery
support.
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from acid
leakage.
5. Batteries are
not deformed
or bulged.
1. Battery
1. Identify the
operating
temperature:
0–45°C
(charging); –
20°C to +45°C
(discharging)
2. If the fault
2. Battery
charge and
discharge
conditions
meet the
requirements
specified in
the battery
specifications.
Check that the
Set parameters
settings of
correctly.
battery
management
parameters meet
the requirements
in the user
manual.
6 O&M
cause of an
abnormal
battery
operating
temperature.
persists,
contact
Huawei
technical
support.