7.
Step 4 Log in to the app.
1.
2.
3.
----End

5.3.3 Initial Startup Password Authentication

When the system type is FusionModule500/800, perform the following steps to
configure it.
Context
Procedure
Step 1 Authenticate the startup password on the WebUI.
Issue 02 (2021-06-30)
NO TE
– If you have set a password when enabling WiFi for the first time, you do not need
to set the password again.
– The WiFi function is disabled by default. If you need to enable the WiFi function,
change the WiFi password to ensure connection security.
– A password that has been used for a long time is more likely to be stolen or
cracked. The risk increases along with the time of use. Change the WiFi password
periodically (recommended: once half a year).
Enter the password currently used for logging in to the WebUI and click
Submit.
Start the PAD app, choose Settings > Network Connection on the login
screen, select WiFi SSID specified on the WebUI, and enter the value of WiFi
Password specified on the WebUI for login.
On the login screen, choose Settings > Communication IP Setting, and
ensure that the IP address is 192.168.245.10.
The user name and login password for the app are the same as those for the
ECC800-Pro WebUI. Specify the user name and password, and tap Login.
NO TE
– After the first login, change the password in time to ensure system access security.
– A password that has been used for a long time is more likely to be stolen or cracked.
The risk increases along with the time of use. Change the password once every three
months.
– It is recommended that you use different user names to log in to both the ECC800-Pro
WebUI and app at the same time. If you use the same user name to log in to the
WebUI and app at the same time, either of them will be forcibly logged out.
The initial startup password authentication is required only during initial
power-on commissioning. If the authentication has been performed
successfully, no authentication is required afterward.
The startup password needs to be authenticated when you restore the default
settings on the WebUI or by pressing keys.
If the startup password authentication is not complete, the ECC800-Pro
WebUI and app cannot be used for commissioning.
When the system type is changed to FusionModule500/800, the startup
password needs to be authenticated again.