Optional) Dehumidifier - Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Type
legs)
Certificat
ion
Running
temperat
ure
Storage
temperat
ure
Storage
humidity
Altitude
a: The neutral wire is not required when the NetCol500-A0265S11E0 works with the
indoor unit NetCol5000-A021H (208 V).
b: Recommended to add the voltage regulator in the front end if the power exceeds this
range. Otherwise, air conditioner will generate alarms frequently and cannot run.
c: CE certification is satisfied when NetCol500-A026SC11E0 works with the indoor unit
NetCol5000-A025 (300 mm width). CB certification is satisfied when
NetCol500-A026SC11E0 works with the indoor unit NetCol5000-A021H (208 V). Other
outdoor units have acquired the CE certification.

3.3.7 (Optional) Dehumidifier

If air cooled in-row air conditioners are used in a smart module whose actual load ratio is less
than 30% of the designed load capacity, it is recommended that one dehumidifier be installed
Issue 04 (2017-06-30)
NetCol5
NetCol50
00-A026
0-A0265S
SC11E0
11E0
RoHS, REACH, CE/CB
Depends on the indoor unit. For details, refer to the product description of
indoor unit user manual.
–40° C to +70° C
5%–95% RH (non-condensing)
0–1000 m. If the altitude exceeds 1000 m, the cooled performance deteriorates.
For the derating details, see the product overview chapter in the user manual of
the indoor unit.
Outdoor unit installation environments are classified as follows based on the harshness:
Class A (controlled environment): indoor environments where temperature and humidity are
controlled, including rooms where people live
Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%
Class C (harsh environment): marine environments within 3.7 km from the coast or outdoor land
environments with simple shielding measures within 1.2 km from a pollution source
Class D (marine environment): environments within 500 m from the coast
The NetCol500-A0365S11E0 and NetCol500-A0265S11E0 outdoor units must not be installed in class
D environments, and other outdoor units must not be installed in class C or class D environments.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
NetCol50
NetCol50
0-A0325C
0-A0365C
11E0
11E0/Net
Col500-A
0365S11E
0
c
3 System Architecture
NetCol50
NetCol50
0-A0385C
0-A0725C
11E0
11E0
76