Setting Procedure Of Real Sensorless Vector Control (Torque Control) - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.4.2
Setting procedure of Real sensorless vector
control (torque control)
Set the motor overheat protection. (Pr.9)
Set the motor capacity and the number of motor poles.
Set the rated motor voltage and frequency.
(Pr.83, Pr.84) (Refer to
Select the control method. (Pr.800) (Refer to
Set the torque command. (Pr.804)
Perform offline auto tuning. (Pr.96)
As required
• Select online auto tuning. (Pr.95) (Refer to
• Adjusting the torque control gain manually (Refer to
Torque control under Real sensorless vector control and vector control
Perform secure wiring.
(Refer to
page
32.)
Make the motor setting. (Pr.71)
(Refer to
page
423.)
Set "0 (standard motor)" or "1 (constant-torque motor)" in Pr.71 Applied
motor.
(Refer to
page
317.)
Set the rated motor current (A) in Pr.9 Electronic thermal O/L relay.
(Pr.80, Pr.81) (Refer to
page
Set the motor capacity (kW) in Pr.80 Motor capacity, and set the
number of motor poles in Pr.81 Number of motor poles. (V/F control
is performed when the setting is "9999" (initial value).)
page
Set the rated motor voltage (V) in Pr.83 Rated motor voltage, and set the
rated motor frequency (Hz) in Pr.84 Rated motor frequency
Enable torque control by setting Pr.800 Control method selection="11"
(torque control) or "12" (speed/torque switch) and torque control becomes valid.
(Refer to
page
190.)
Set the speed limit. (Pr.807)
(Refer to
page
195.)
(Refer to
page
426.)
Test run
page
Sensorless
Sensorless
Sensorless
137.)
426)
page
137)
444.)
page
201)
187
PARAMETERS
5