(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
5.8
(F) Setting of acceleration/deceleration
time and acceleration/deceleration pattern
Purpose
To set the motor acceleration/
deceleration time
To set the acceleration/
deceleration pattern suitable
for an application
To command smooth speed
transition with terminals
To set the starting frequency
To set optimum acceleration/
deceleration time automatically
To set V/F pattern for lift
automatically
5.8.1
Setting the acceleration and deceleration time
The following parameters are used to set motor acceleration/deceleration time.
Set a larger value for a slower acceleration/deceleration, and a smaller value for a faster acceleration/deceleration.
For the acceleration time at automatic restart after instantaneous power failure, refer to Pr.611 Acceleration time at a
restart
(page
515).
Pr.
Name
20
Acceleration/deceleration
F000
reference frequency
21
Acceleration/deceleration
F001
time increments
16
Jog acceleration/
F002
deceleration time
611
Acceleration time at a
F003
restart
7
Acceleration time
F010
8
Deceleration time
F011
44
Second acceleration/
F020
deceleration time
45
Second deceleration time
F021
147
Acceleration/deceleration
F022
time switching frequency
110
Third acceleration/
F030
deceleration time
P.F000 to P.F003,
P.F010, P.F011,
Acceleration/
P.F020 to P.F022,
deceleration time
P.F030, P.F031,
P.F040, P.F070,
P.F071, P.G264
P.F100,
Acceleration/
P.F200 to P.F203,
deceleration pattern and
P.F300 to P.F303,
backlash measures
P.F400 to P.F403
Remote setting function P.F101
Starting frequency and
P.F102, P.F103
start-time hold
Automatic acceleration/
P.F500,
deceleration
P.F510 to P.F513
Lift operation
(Automatic acceleration/
P.F500, P.F510, P.F520
deceleration)
Initial value
Setting range
60 Hz
1 to 590 Hz
0
0
1
0.5 s
0 to 3600 s
9999
0 to 3600 s, 9999
5 s

0 to 3600 s
15 s

5 s

0 to 3600 s
15 s

5 s
0 to 3600 s
0 to 3600 s
9999
9999
0 to 590 Hz
9999
9999
0 to 3600 s
9999
9999
Parameter to set
Pr.7, Pr.8, Pr.16,
Pr.20, Pr.21, Pr.44,
Pr.45, Pr.110, Pr.111,
Pr.147, Pr.611, Pr.791,
Pr.792, Pr.1103,
Pr.1349
Pr.29,
Pr.140 to Pr.143,
Pr.380 to Pr.383,
Pr.516 to Pr.519
Pr.59
Pr.13, Pr.571
Pr.61 to Pr.63, Pr.292
Pr.61, Pr.64, Pr.292
Description
Set the frequency that will be the basis of
acceleration/deceleration time. As acceleration/
deceleration time, set the frequency change time from
a stop status to Pr.20.
Increment: 0.1 s
Increment: 0.01 s
Set the acceleration/deceleration time for JOG
operation (from stop status to Pr.20).
Refer to
page
312.
Set the acceleration time for restart (from stop status
to Pr.20).
When "9999" is set, standard acceleration time (like
Pr.7) is applied as the acceleration time at restart.
Refer to
page
515.
Set the motor acceleration time (from stop status to
Pr.20).
Set the motor deceleration time (from Pr.20 to stop
status).
Set the acceleration/deceleration time when the RT
signal is ON.
Set the deceleration time when the RT signal is ON.
Acceleration time = deceleration time
Set the frequency where the acceleration/deceleration
time switches to the time set in Pr.44 and Pr.45.
No function
Set the acceleration/deceleration time when X9 signal
is ON.
Third acceleration/deceleration is disabled.
Refer
to page
269
274
279
283,
284
285
288
Select the increment for the
acceleration/deceleration time
setting.
269
PARAMETERS
5
GROUP
F