Mitsubishi Electric 800 Series Instruction Manual page 511

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(A) Application parameters
NOTE
• Normally, set Pr.7 Acceleration time and Pr.8 Deceleration time to "0 s". When the Pr.7 and Pr.8 settings are large, dancer
control response becomes slow during acceleration/deceleration.
• The Pr.127 PID control automatic switchover frequency setting is enabled. The larger setting value between Pr.7 and
Pr.44 is used as the acceleration time during normal operation. For the deceleration time, the larger setting value between
Pr.8 and Pr.45 is used. (For the details of Pr.127, refer to
• If an automatic restart after instantaneous power failure is activated during dancer control, E.OC[] or E.OV[] is likely to occur.
In such case, disable the automatic restart after instantaneous power failure function (Pr.57 = "9999").
Connection diagram
• Sink logic
• Pr.128 =41
• Pr.182 =14
• Pr.193 =14
• Pr.194 =15
• Pr.133 =set point

The main speed command differs according to each operation mode (External, PU, communication).

The output signal terminal to be used differs according to the Pr.190 to Pr.196 (Output terminal function selection) setting.

The input signal terminal to be used differs according to the Pr.178 to Pr.189 (Input terminal function selection) setting.

The AU signal need not be input.
Dancer control operation selection (Pr.128)
Pr.128
PID action
setting
0
PID invalid
40
Reverse action
41
Forward action
42
Reverse action
43
Forward action
Others
Refer to
page

When Pr.133  "9999", the Pr.133 setting is valid.
• To enable dancer control, set "40 to 43" in Pr.128 PID action selection.
• Dancer control is enabled only when the PID control valid terminal (X14) signal turns ON when "14" is set in one of Pr.178
to Pr.182 (Input terminal function selection) and X14 signal is assigned.
When the X14 signal is not assigned, dancer control is enabled only by the Pr.128 setting.
• Input the main speed command (External, PU, Communication). Dancer control is also supported by the main speed
command in all operation modes.
• Input the set point between the terminals 2 and 5 (the setting can be selected using Pr.133 or Pr.609) and input the
measured value signal (dancer roll position detection signal) between the inverter terminals 4 and 5 (the setting can be
selected using Pr.610).
• The action of Pr.129 PID action selection, Pr.130 PID integral time, Pr.131 PID upper limit, Pr.132 PID lower limit and
Pr.134 PID differential time is the same as PID control action. In the relationship between the control amount (%) and
frequency in PID control, 0% and 100% are equivalent to the frequencies set to Pr.902 and Pr.903, respectively.
510
PARAMETERS
Power supply
Forward rotation
Reverse rotation
PID control selection
Main speed command
setting potentiometer
Feedback value of
dancer roll position
Additive
method
-
-
Fixed
Set by Pr.133 or Input by terminal
selected by Pr.609
Ratio
488.
page
488.)
Inverter
MCCB
R/L1
S/L2
T/L3
STF
STR
RH(X14)
∗3
SD
∗2
∗2
10
2
∗1
5
4
∗4
Set point input

Motor
U
V
IM
W
(FUP)FU
Upper limit
(FDN)OL
Lower limit
Output signal common
SE
Measured value input
-
Input by terminal selected by Pr.610

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents