(E) Environment setting parameters
Pr.557 Current average value monitor signal output reference current setting
• Set the reference (100%) for outputting the output current average value signal. The signal output time is calculated with
the following formula.
Output current average value
Pr.557 setting value
The output time range is 0.5 to 9 s. When the output current average value is less than 10% of the setting value in Pr.557,
the output time is 0.5 s, and when it is more than 180%, the output time is 9 s.
For example, when Pr.557 = "10 A" and the output current average value is 15 A:
15 A/10 A  5 s = 7.5 s, thus the current average value monitor signal is Low output in 7.5 s intervals.
(s)
9
0.5
10
180
Output current average value
Pr.503 Maintenance timer 1 output
• After LOW output of the output current value is performed, HIGH output of the maintenance timer value is performed. The
maintenance timer value output time is calculated with the following formula.
Pr.503  100
 5 s (Maintenance timer value 100%/5 s)
40000 h
The output time range is 2 to 9 s. When Pr.503 is less than 16000 h, the output time is 2 s, and when it is more than 72000
h, the output time is 9 s.
(s)
9
2
16000
72000
Maintenance timer value
NOTE
• Masking of the data output and sampling of the output current are not performed during acceleration/deceleration.
• If constant speed changes to acceleration or deceleration during start pulse output, it is judged as invalid data, and HIGH
output in 3.5 s intervals is performed for the start pulse and LOW output in 16.5 s intervals is performed for the end signal.
After the start pulse output is completed, minimum 1-cycle signal output is performed even if acceleration/deceleration is
performed.
Output frequency
Previous cycle
Y93
signal
Start pulse
Output as high pulse shape for 3.5 s
• If the output current value (inverter output current monitor) is 0 A at the completion of the 1-cycle signal output, no signal is
output until the next constant-speed state.
• Under the following conditions, the Y93 signal is output with Low output in 20 s intervals (no data output).
- When acceleration or deceleration is operating at the completion of the 1-cycle signal output
- When automatic restart after instantaneous power failure (Pr.57 Restart coasting time  "9999") is set, and the 1-cycle
signal output is completed during the restart operation
- When automatic restart after instantaneous power failure (Pr.57  "9999") is set, and the restart operation was being
performed at the completion of data output masking
• Pr.686 Maintenance timer 2 and Pr.688 Maintenance timer 3 cannot be output.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
???????
Pr.57 Restart coasting time
Pr.190 to Pr.196 (Output terminal function selection)
Pr.503 Maintenance timer 1, Pr.686 Maintenance timer 2, Pr.688 Maintenance timer 3
268
PARAMETERS
 5 s
(Output current average value 100%/5 s)
(%)
(h)
The speed is changed to deceleration from
the constant speed during start pulse output
Invalid cycle (20 s)
page 515
page 370
Time
Next cycle
End signal
Output as low pulse shape for 16.5 s
page 266