Huawei SmartLogger1000 User Manual page 163

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

SmartLogger1000
User Manual
Figure 7-76 Disable reactive power output
Remote Control Power Factor
The SmartLogger scans all the dry contact signals sent from the power dispatching related
devices (the wireless receiver controller or power carrier communications devices), analyzes
the valid command data identified by the inverters, and sends the data to all the inverters
connected to the SmartLogger.
Set Reactive Power Control Mode to Remote control power factor, as shown in
7-77.
Ensure that the SmartLogger is properly connected to the ripple control receiver before you
set Reactive Power Control Mode to Remote control power factor. For details, see
Connecting the SmartLogger to a Ripple Control
Issue 04 (2013-12-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Receiver.