6.2.14 Managing Devices

This topic describes how to search for, add, or delete devices that are connected to the
SmartLogger on the monitoring panel.
Context
Procedure
Issue 04 (2013-12-15)
Provided that all the inverters are correctly connected to the SmartLogger and that all the
communications parameters are correctly set, the SmartLogger can perform the
automatic search and detect all the connected inverters.
After you add, delete, or replace a device, or change the RS485 address, search for
devices again or restart the SmartLogger (the SmartLogger automatically searches for
devices after it restarts).
The environmental monitoring instrument cannot be detected automatically. You need to
add this device manually.
For devices that no longer exist in the PV power system, perform Remove Devices in
time to save the system resources.
The RS485 addresses of all inverters are set the same when they are delivered. If the
firmware version of the SUN2000 is later than V100R001C00SPC010, you can perform
the automatic address assignment on the SmartLogger. If any two RS485 addresses
overlap, the SmartLogger automatically reassigns different addresses, which facilitates
remote site setup and improves the maintenance efficiency.
The following table describes the procedure for managing the devices. The parameter
values in the following figures are for reference only.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Operation Procedure
7. After determining the Target Version,
press
.
NOTICE
Before upgrading the SUN2000, ensure that it is
correctly connected to the PV arrays.
After upgrading the SmartLogger, restart
the SmartLogger.
After upgrading the inverter, press