UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Figure 6-103 Installing copper bar protection components (400–600 kVA)
Figure 6-104 Installing copper bar protection components (800 kVA)
Step 3 Reinstall the UPS rear door panels.
----End
6.8 Installing Cables for the TN-C System
If the TN-C system is adopted, short-circuit the input N and PE, and connect the
input PE and N to terminals on the N bar.
Recommended cable cross-sectional area: 240 mm