1.8 Others

Issue 03 (2021-08-03)
Keep the lithium battery loop disconnected during installation and
maintenance.
Do not charge a battery when the ambient temperature is below the lower
limit of the operating temperature (charging is forbidden at 0°C). Low-
temperature charging may cause crystallization, which will result in a short
circuit inside the battery.
Use batteries within the allowed temperature range. Otherwise, the battery
performance and safety will be compromised.
Do not throw a lithium battery in fire.
When maintenance is complete, return the waste lithium battery to the
maintenance office.
Exercise caution when manually shutting down the UPS inverter for
transferring to bypass mode, or when adjusting the UPS output voltage level
or frequency. Doing so may affect the power supply to equipment.
Exercise caution when setting battery parameters. Incorrect settings will affect
the power supply and battery lifespan.