Huawei UPS5000-H User Manual page 77

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Table 6-3 Recommended power cable cross-sectional areas (200–500 kVA)
Item
Mains input
Mains input
current (A)
Recomme
nded
cross-
sectional
area
(mm
Bypass input
Bypass input
current (A)
Recomme
nded
cross-
sectional
area
(mm
Output
Output current (A)
Recomme
nded
cross-
sectional
area
(mm
Battery
Nominal battery
input (lead-
discharge current
acid battery)
(A)
Maximum battery
discharge current
(A)
Recomme
nded
cross-
sectional
area
(mm
Issue 03 (2021-08-03)
200 kVA
372
L1
2 x 95
L2
2 x 95
L3
2 x 95
2
)
N
2 x 95
PE
95
304
L1
2 x 95
L2
2 x 95
L3
2 x 95
2
)
N
2 x 95
PE
95
304
U
2 x 95
V
2 x 95
W
2 x 95
2
N
2 x 95
)
PE
95
443
531
+
2 x 120
-
2 x 120
PE
120
2
)
Copyright © Huawei Technologies Co., Ltd.
300 kVA
400 kVA
557
743
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
150
240
456
608
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
150
240
456
608
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
2 x 150
2 x 240
150
240
665
877
796
1062
2 x 185
2 x 240
2 x 185
2 x 240
185
240
6 Installation
500 kVA
929
3 x 185
3 x 185
3 x 185
3 x 185
240
760
3 x 185
3 x 185
3 x 185
3 x 185
240
760
3 x 185
3 x 185
3 x 185
3 x 185
240
1108
1327
3×185
3 x 185
240
69