User Manual (100 kVA Power Modules)
Step 2 Start the inverter. Choose Common Functions > Inv. ON. The system transfers to
inverter mode.
----End

7.9 T/H Sensor Settings

Context
The ambient T/H sensor has been installed by referring to the installation section.
The ambient T/H sensor can also be used as a battery temperature sensor. The
monitoring module distinguishes these two types of sensors through their DIP
switch settings.
Procedure
Step 1 Set the DIP switch.
Figure 7-20 DIP switch
(1) DIP switch
Each ambient T/H sensor has a unique DIP switch address, ranging from 32 to 44.
A DIP switch has six binary toggle switches. The bit on the leftmost is the most
significant bit, and the bit on the rightmost is the least significant bit. Bit 1
indicates ON, and bit 0 indicates OFF.
Issue 03 (2021-08-03)
NO TE
The RS485_R DIP switch is used to enable a build-out resistor so that the ambient T/H
sensor can communicate with the controller. If there are no more than four ambient T/H
sensors on the bus, the RS485_R DIP switch does not need to be set. If there are more than
four, flip the RS485_R DIP switch of the ambient T/H sensor furthest from the UPS to ON.
DIP switch settings on ambient T/H sensors
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
170