7.1.8 (Optional) Setting the Intelligent Detection Card
Prerequisites
An intelligent detection card is installed.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set
Intelligent detection module to Enable.
----End
7.1.9 (Optional) Setting the Top Outlet Fan
Prerequisites
A top outlet kit is deployed.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Top outlet
fan to Enable.
----End
7.2 Shutting Down and Powering Off the UPS
Context
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut
down; if the bypass is abnormal, the UPS supplies no power after the inverter is
shut down. Before shutting down the UPS, ensure that all loads have been shut
down.
Procedure
Step 1 Shut down the inverter.
●
Issue 03 (2021-08-03)
NO TE
If MUE06A connection is set to Enable and the backfeed protection card fails to
communicate with the UPS, the system reports a Dry contact board fault alarm.
NO TICE
Shutting down the inverter on the LCD
Choose Common Functions > Inv. OFF. After confirmation, the inverter is
shut down.