UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Figure 6-10 800 kVA cabinet copper bar layout and specifications (unit: mm)
(1) Battery wiring busbar
(4) Busbar of the same power
source for mains and bypass
inputs
In a parallel system, the length and specifications of power cables on each UPS
should be the same to achieve current equalization in bypass mode. The power
cables include bypass input power cables and UPS output power cables.
Table 6-2 Power terminal connection requirements
Port
Connection Method
Mains input
Crimped DT terminal
Bypass input
Crimped DT terminal
Battery input
Crimped DT terminal
Output
Crimped DT terminal
PE
Crimped DT terminal
Equipotential
Crimped DT terminal
ground point
6.1.4.1 380 V AC/400 V AC/415 V AC Voltage System
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
Issue 03 (2021-08-03)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(2) PE wiring busbar
(5) Bypass input wiring busbar (6) Output wiring busbar
Bolt
Specifications
M16
M16
M16
M16
M12
M6
(3) Mains input wiring busbar
Bolt Length
Torque
55 mm
120 N·m
55 mm
120 N·m
55 mm
120 N·m
55 mm
120 N·m
30 mm
47 N·m
12 mm
4.5 N·m