UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Procedure
Step 1 Set the language, time, network parameters, system parameters, and battery
parameters on the Settings Wizard screen.
Set system parameters with caution because the settings determine whether the
UPS can operate normally.
● Set Single/Parallel after double check. Incorrect settings may affect the normal
● Output voltage level refers to the line voltage level. Set it based on site
● Set Output frequency correctly. Otherwise, loads may be affected and the UPS
● Set all battery parameters correctly based on site requirements. Battery
Figure 7-1 Settings Wizard
Issue 03 (2021-08-03)
NO TICE
UPS operation.
requirements.
may not work properly.
parameter settings are critical to battery maintenance, battery lifespan, and
UPS discharge time.
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
151