Table 4-5 Port description
Silk Screen
PARALLEL
BSC
Table 4-6 Indicator description
Indicator
NORMAL
ALM
FAULT
Issue 03 (2021-08-03)
Description
The PARALLEL port transmits parallel signals between racks.
The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,
ensuring that two buses can switch with each other.
BSC cables are hot-swappable.
NO TE
No parallel cable is required for a single UPS.
Colo
Status
r
Gree
Steady on
n
Blinking
at 0.5 Hz
Off
Blinking
at 4 Hz
Yello
Steady on
w
Off
Red
Steady on
Off
Copyright © Huawei Technologies Co., Ltd.
Description
This ECM is the active ECM.
This ECM is the standby ECM and it is ready.
This ECM is not ready or the software of this
ECM is being upgraded.
The ECM software is being upgraded or not
configured.
The ECM has a minor alarm, but it does not
need to be replaced.
The ECM has no minor alarm or the software of
the ECM is being upgraded.
The ECM has a critical alarm.
The ECM has no critical alarm or the software
of the ECM is being upgraded.