UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Indicator
Alarm
indicator
Fault
indicator
Table 4-2 Specifications
Item
Rated output capacity
Dimensions (H x W x D)
Weight
4.2 Bypass Module
The UPS supplies power through the bypass under the following circumstances:
●
●
●
●
●
Issue 03 (2021-08-03)
Colo
Status Description
r
Blinki
ng at
short
interv
als
Off
Yello
Stead
w
y on
Off
Red
Stead
y on
Off
The S-ECO or ECO mode is used and the bypass voltage is within the specified
range.
The power module overload times out.
Both active and standby energy control modules (ECMs) in the system are
abnormal.
The system runs abnormally.
The power supply is switched is to the bypass manually.
Copyright © Huawei Technologies Co., Ltd.
The module is not configured, the inverter
software and rectifier software are being
upgraded, or the inverter software is being
upgraded (blinking at 4 Hz, on for 0.125s and off
for 0.125s).
The software is being upgraded.
A minor alarm is generated for the inverter or
rectifier.
There is no minor alarm for the inverter or
rectifier, or the software is being upgraded.
A critical alarm is generated for the inverter or
rectifier.
There is no critical alarm for the inverter or
rectifier, or the software is being upgraded.
Specifications
● 200 V AC/208 V AC/210 V AC voltage system:
50 kVA/50 kW
● 380 V AC/400 V AC/415 V AC/480 V AC
voltage system: 100 kVA/100 kW
130 mm x 442 mm x 750 mm
< 55 kg
4 Component Description