UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Table 6-7 Recommended input/output circuit breakers
Component
Specifications
Name
a
(100 kVA)
Mains input
400 A/3P
circuit breaker
Bypass input
400 A/3P
circuit breaker
Downstream
400 A/3P
output circuit
breaker
a: recommended model when the short-circuit current where the circuit breaker is located is less
than 65 kA
6.1.4.3 480 V AC Voltage System
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
Table 6-8 Recommended power cable cross-sectional areas (200–500 kVA)
Item
Mains input
Mains input
current (A)
Issue 03 (2021-08-03)
–
Routing mode: The cables are routed over a tray or bracket in a single
layer (E in IEC 60364-5-52). The distance between cables should be
greater than twice the cable diameter. Routing mode: The cables are
routed over a tray or bracket in a single layer (E multi-core and G single-
core in IEC 60364-5-52).
–
Ambient temperature: 30°C
–
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%.
–
Conductor insulation: PVC insulation
–
The 90°C flexible cables with copper conductors are used.
–
It is recommended that AC power cables be no longer than 30 meters
and DC power cables be no longer than 50 meters.
Specifications
a
(150 kVA)
630 A/3P
630 A/3P
630 A/3P
NO TE
● The input circuit breakers recommended are for reference only.
● If multiple loads are connected, use recommended specifications for branch circuit
breakers.
● The circuit breaker selection principle is to protect loads and cables, and the cascading
principle is to achieve specific protection.
200 kVA
294
Copyright © Huawei Technologies Co., Ltd.
Specifications
Specifications
a
a
(200 kVA)
(250 kVA)
800 A/3P
1000 A/3P
630 A/3P
800 A/3P
630 A/3P
800 A/3P
300 kVA
400 kVA
441
588
6 Installation
Specifications
a
(300 kVA)
1250 A/3P
1000 A/3P
1000 A/3P
500 kVA
735
75