Functions
<Timing chart>
Test / Reset input
Override input
Muting sensor A / C
Muting sensor B / D
Override function
Muting auxiliary
output
Sensing object
(within protection area)
Control output
(OSSD 1 / 2)
Notes: 1) If the muting indicator does not turn ON after 1 sec. when the muting indicator diagnosis function is
valid, the override function is invalid. When the muting indicator diagnosis function is invalid, the muting
function is valid 3 sec. after the input conditions of muting sensors A (C) and B (D) are satisfied.
2) The range depends on the number of beam channels and number of series connections.
112
Open
Shorted
1 sec. or less
Open
Shorted
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Yes
No
ON
OFF
3 to 4 sec. (Note 1)
Override time: Max. 60 sec.
60ms or less
© Panasonic Industrial Devices SUNX Co., Ltd. 2017
0.1 sec. or less
60ms or less
10 to 60ms (Note 2)