Huawei UPS5000-E-12 User Manual page 207

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Check Item
Operating environment
Liquid crystal display
(LCD)
Cleanliness
Parameter configuration
Power cables and terminals
(between the UPS and the
power distribution cabinet)
To prevent system failures caused by the deterioration of some key UPS components, you are
advised to check the key components on a regular basis and replace them within the service
life.
Table 6-4
replacement intervals.
Table 6-4 Service life parameters for replaceable components and recommended replacement
intervals
Key Component
Power module
Bypass module
Fan
Valve regulated lead acid
(VRLA) battery
Issue 10 (2015-09-15)
Expected Result
Ambient temperature:
0–40° C
Humidity: 0–95% RH
(non-condensing)
According to the status
icons on the LCD, all units
are operating properly. No
fault or alarm information is
found in the active and
historical alarm records.
Wipe the cabinet surface
using a white paper and the
paper does not turn black.
The configuration of the
output voltage grade,
frequency, number of
batteries, and battery
capacity meets
requirements.
The insulation layer of
cables is intact and terminals
are free from noticeable
sparks.
lists the service life parameters for key components and recommended
Design Service Life
≥ 15 years (131,000 hours)
≥ 15 years (131,000 hours)
≥ 7 years (62,000 hours)
5 years
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Routine Maintenance
Troubleshooting
If the humidity and
temperature are
abnormal, check the air
conditioner status.
If the input voltage is
abnormal, check the
power grid status and
input cable connection.
If an alarm is present, rectify
the fault by checking the
device status and
parameters.
Remove the dust, especially
from the air filter on the
front door, or replace the air
filter.
Reset the parameters.
Replace the cables.
Secure output terminals.
Recommended
Replacement
Interval
7–10 years
7–10 years
5–6 years
3–4 years
198

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents