UPS5000-E-(40 kVA-320 kVA)
User Manual
Step 3 On the Maintenance screen, tap Battery Maint., as shown in
Step 4 Tap Start on the right of Shallow Dis. Test to start a shallow discharge test, as shown in
Figure
Figure 5-24 Starting a shallow discharge test
----End

5.6.3 Capacity Test

Context
Before a capacity test, ensure that:
Issue 10 (2015-09-15)
Table 4-4
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
5-24.
When the battery test is complete, the test data is used as common test data. You need to record the data
obtained from the latest five tests.
The shallow discharge test stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the alarm threshold (calculated in real time).
The load change rate exceeds 10%.
An alarm is generated.
You tap Stop on the right of Shallow Dis. Test.