UPS5000-E-(40 kVA-320 kVA)
User Manual

2.2 Benefits

High Stability and Reliability
High Flexibility and Intelligent Management
Issue 10 (2015-09-15)
Output capacity: 40 kVA, 80 kVA, or 120 kVA
UPS5000-E-200K-F200
Output capacity: 40 kVA, 80 kVA, 120 kVA, 160 kVA, or 200 kVA
UPS5000-E-320K-F320
Output capacity: 40 kVA, 80 kVA, 120 kVA, 160 kVA, 200 kVA, 240 kVA, 280 kVA, or
320 kVA
UPS5000-E-320K-F320T
Output capacity: 40 kVA, 80 kVA, 120 kVA, 160 kVA, 200 kVA, 240 kVA, 280 kVA, or
320 kVA
The UPS5000-E-120K-F120 can expand to a maximum of 120 kVA and is at least 40 kVA. Cables
are routed from the top or bottom.
The UPS5000-E-200K-F200 can expand to a maximum of 200 kVA and is at least 40 kVA. When
mentioning the UPS5000-E-200K-F200, this document emphasizes its output capacity of 160 kVA
or 200 kVA. Cables are routed from the top or bottom.
The UPS5000-E-320K-F320 can expand to a maximum of 320 kVA and is at least 40 kVA. When
mentioning the UPS5000-E-320K-F320, this document emphasizes its output capacity of 240 kVA,
280 kVA, or 320 kVA. Cables are routed from the bottom (a top entry cabinet can be installed.)
The UPS5000-E-320K-F320T can expand to a maximum of 320 kVA and is at least 40 kVA. When
mentioning the UPS5000-E-320K-F320, this document emphasizes its output capacity of 240 kVA,
280 kVA, or 320 kVA. Cables are routed from the top.
The UPS is suitable for poor power grids because it supports a wide range of input
frequencies which is 40–70 Hz. The UPS works at full load when the line voltage is
305–485 V AC and is linearly derated when the line voltage is 138–305 V AC (excluding
305 V AC).
The UPS5000-E has 5 kA lightning protection, higher than the industry level 2 kA.
The control module (CM) uses a redundant design. Fans have high fault tolerance
capability: When a single fan is faulty, the UPS5000-E works at 50% load; when two
fans are faulty, the UPS5000-E works at 30% load.
The UPS5000-E has a high inverter overload capability.
105% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
The UPS5000-E has a high bypass overload capability.
Load ≤ 135%: run continuously in bypass mode at 30°C or less
1000% load: run in bypass mode for 100 ms
The built-in parallel card supports parallel connection of UPS5000-Es. Built-in bus
synchronization controllers (BSCs) support dual-bus configuration.