UPS5000-E-(40 kVA-320 kVA)
User Manual
Figure 3-57 EPO NO connection
3.2.13.3 (Optional) Connecting the BCB Box
Open the cover on the BCB box, and connect the BCB ports on the dry contact card to the
control signal ports on the BCB box. For details, see the PDC-(0250, 0400, 0630)
DC0384BXA BCB Box User Manual or PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 BCB-BOX User Manual.
3.2.13.4 (Optional) Connecting the Output PDC
Connect the SWITCH STATUS ports on the dry contact card to the dry contact ports on the
output PDC. For details, see the PDC-0630ACV4OUA Power Distribution Unit User Manual.
3.2.13.5 (Optional) Connecting the Input PDC
Connect the ports on the dry contact card to the dry contact ports on the input PDC. For
details, see the PDC-0630ACV4INA Power Distribution Unit User Manual.
3.2.13.6 (Optional) Connecting the Backfeed Protection Card
For details, see the UPS Backfeed Protection Card User Manual.
3.2.13.7 Connecting Communications Cables
Procedure
Step 1 Connect the MUS05A port on the MDU to the MDU port on the monitoring interface card, as
shown in