5.12.2 WebUI

Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings. Under Intelligent Power Settings, set Intelligent
Power Supply to Enabled, as shown in
Figure 5-56 Intelligent power parameters on the WebUI
Issue 10 (2015-09-15)
If the battery voltage is greater than D.G. startup batt. volt., the UPS exits intelligent mode and
triggers D.G. shutdown signals. If the battery voltage is less than D.G. startup batt. volt., a dialog
box is displayed, indicating potential risks. Tap OK to exit intelligent mode.
To disable the D.G. from the UPS system, set Intelligent Power Supply to Disabled. The system
changes Working mode to Normal mode, Intra-rack power unit start delay (s) to 5, Output freq.
track rate (Hz/s) to 0.6, Input adaptability to Non-strong input, D.G. mode to Disabled, and D.G.
connection [GEN] to Disabled. You can change the values.
Intelligent Power Supply parameter
The value can be Enabled or Disabled. The default value is Disabled.
ATS parameter
The value can be Connected or Not connected. When the value is Connected, the UPS
works in the ATS scenario; when the value is Not connected, the UPS works in the reuse
scenario. The default value is Connected. This parameter is available only after you set
Intelligent Power Supply to Enabled.
D.G. startup batt. volt. (V/cell) parameter
The value ranges from 1.80 to 2.00. The default value is 1.80. This parameter is available
only after you set Intelligent Power Supply to Enabled.
Set the preceding three parameters when you connect the D.G. to the UPS.