Optional Components - Huawei UPS5000-E-12 User Manual

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual

2.6 Optional Components

Component
Input PDC
Output PDC
BCB box
Battery bus
bar (BBB) box
Surge
Issue 10 (2015-09-15)
Model
PDC-0630ACV4INA
PDC-0630ACV4OUA
PDC-0250DC0384BXA
PDC-0400DC0384BXA
PDC-0630DC0384BXA
PDU8000-0125DCV8-B
XA001
PDU8000-0250DCV8-B
XA001
PDU8000-0400DCV8-B
XA001
PDU8000-0630DCV8-B
XA001
PDU8000-0800DCV8-B
XA001
PDU8000-0630DCV8-B
GA001
PDU8000-1250DCV8-B
GA001
PDU8000-2000DCV8-B
GA001
N/A
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Function
Provides one 4-pole 630 A input
ATS, two 3-pole 400 A mains output
molded case circuit breakers
(MCCBs), and two 3-pole 400 A
bypass output MCCBs.
Measures and displays electrical
parameters, such as the three-phase
input voltage, current, and power
factor (PF).
Provides signal ports to report the
status of circuit breakers, and
provides three-phase power indicators
to display the power status.
Provides two 4-pole 400 A input
MCCBs and one 3-pole 630 A
maintenance bypass circuit breaker.
Measures and displays electrical
parameters, such as the three-phase
input voltage, current, and PF.
Provides signal ports to report the
status of circuit breakers, and
provides three-phase power indicators
to display the power status.
Controls the connection between
battery strings and the UPS.
Provides overload protection,
short-circuit protection, and remote
trip control.
Converges the energy from multiple
battery strings.
Improves the UPS surge protection
2 Overview
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents