Optional) Backfeed Protection Card; Optional) Dry Contact Extended Card; Monitoring Interface Card - Huawei UPS5000-E-12 User Manual

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual

2.4.2.4 (Optional) Backfeed Protection Card

Energy backfeed may be dangerous for the UPS, loads, and maintenance personnel. When
backfeed occurs, the backfeed protection card triggers alarm signals or quickly disconnects
the backfeed loop. The backfeed protection card uses relay contact signals. The signal ports
support any power signals with a voltage of no more than 240 V AC and a current of less than
4 A. For details, see the UPS Backfeed Protection Card User Manual.

2.4.2.5 (Optional) Dry Contact Extended Card

The dry contact extended card provides five signal output ports and five signal input ports.
For details, see the UPS Dry Contact Extended Card User Manual.

2.4.2.6 Monitoring Interface Card

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
battery monitoring unit (BMU) port, FE port, battery temperature monitoring port, and
network management port. Interworking with the monitoring interface card, the MDU
monitors the UPS, configures parameters, delivers commands, reports information, and
displays the UPS key information and parameters on the LCD.
Figure 2-13
Figure 2-13 Monitoring interface card
Table 2-4
Table 2-4 Ports on the monitoring interface card
Port
DO_1
DO_2
Issue 10 (2015-09-15)
shows the monitoring interface card.
describes the ports on the monitoring interface card.
Silk
Description
Screen
NO
DO indicates critical alarms, minor alarms, bypass mode,
battery mode, low battery voltage, or D.G. control. DO_1
COM
indicates any of the six meanings (except for D.G. control); by
default, it indicates critical alarms. The maximum voltage is 30
V DC, and the maximum current is 1 A.
NO
DO indicates critical alarms, minor alarms, bypass mode,
battery mode, low battery voltage, or D.G. control. DO_2
COM
indicates any of the six meanings (except for D.G. control); by
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Overview
25