Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
You can set hibernation mode on the LCD and WebUI.

5.11.1 LCD

Procedure
Step 1 On the main screen, tap System Info. and
Step 2 Tap Advanced Param.. Tap
5-44.
Figure 5-44 Hibernation parameters on the LCD
Step 3 On the LCD, set Para. sys. hibernate to Enabled. A confirmation message and security
warning are displayed, as shown in
Issue 10 (2015-09-15)
Before you start hibernation mode, ensure that the load power is stable. When the system
load power fluctuation is greater than the rated capacity of half a module (for example, the
single-phase load fluctuation is greater than 6.67 kVA for a 40 kVA module), the UPS may
enter and exit from hibernation mode repeatedly.
Before you start hibernation mode, check the number of redundant power modules and the
number of redundant UPSs. If the number is insufficient, the UPS may not enter
hibernation mode.
If you have not logged in, enter a user name and password, and tap
displayed.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
. The Settings screen is displayed.
or
to browse the parameters, as shown in
Figure 5-45
and
Figure
5 Operations
on the login screen
5-46.
Figure
182

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents