Bottom Cable Routing - Huawei UPS5000-E-12 User Manual

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Figure 3-34 Routing signal cables from the top of the cabinet
----End

3.2.8.2 Bottom Cable Routing

Context
The UPS5000-E-320K-F320T does not support cable routing from the bottom.
The UPS5000-E-120K-F120, UPS5000-E-200K-F200, and UPS5000-E-320K-F320 use the
same bottom cable routing mode. Bottom cable routing for the UPS5000-E-200K-F200 is
used as an example. To route cables from the bottom of the UPS5000-E-200K-F200, perform
the following steps:
Procedure
Step 1 Open the front door, and remove the cover from the power distribution subrack, as shown in
Figure
Issue 10 (2015-09-15)
If you route cables through the bottom of the cabinet, ensure sufficient space.
After routing cables, use fireproof mud to fill in the gap between the cables and the
cabinet.
3-35.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation
68