1.2.2 Battery Safety

Before installing, operating, or maintaining batteries, read the battery
manufacturer's instructions. Observe the safety precautions provided in this
document which are supplemental to the safety instructions provided by the
battery manufacturer.
Issue 02 (2022-07-18)
capacitive loads, pure inductive loads, and half-wave rectification loads. A UPS
does not apply to regeneration loads.
The UPS can be configured with a backfeed protection dry contact to work
with an external automatic circuit breaker, preventing the voltage from
flowing back to input terminals over static bypass circuits. If the installation
and maintenance personnel do not need backfeed protection, paste labels on
external mains and bypass input switches, informing that the UPS is
connected to a backfeed protection card. Disconnect the backfeed protection
card from the UPS before operating the UPS.
The upstream power distribution of the UPS should comply with IEC
60364-4-41.
The UPS operating environment must meet the requirements for the climate
indicator, mechanically active substance indicator, and chemically active
substance indicator in ETSI EN 300 019-1 class 3.6.
Ensure that the equipment is used in an environment that meets the product
design specifications (including power grid, temperature, and humidity).
Otherwise, the equipment may become faulty, and the resulting equipment
malfunction and component damage are not covered under the warranty.
After unpacking the UPS, you are advised to power it on as soon as possible.
If the UPS is not in operation, take appropriate measures to prevent moisture,
dust, and foreign matter from entering the UPS.
Any operation on any electrical equipment in an environment that has
inflammable air can cause extreme danger. Strictly obey the operating
environmental requirements specified in related user manuals when using or
storing the equipment.
Do not use the UPS in the following places:
Environments that are close to flammable or explosive materials, dust,
corrosive gases or dust, conductive or magnetic dust, abnormal vibration,
or collision
Rooms or outdoor environments where temperature and humidity are
not controlled (with high temperature, low temperature, moisture, direct
sunlight, or heat sources)
Non-confined environments near the ocean (0–3.7 km) and indoor or
semi-indoor environments where the temperature and humidity are not
controllable, such as simple equipment rooms, civil houses, garages,
corridors, and direct ventilation cabinets near the ocean; or houses with
only roofs, railway station platforms, gymnasiums, and aquariums
Environments that are conducive for the growth of microorganisms such
as fungus or mildew
Environments where rodents (such as mice) and insects exist
Copyright © Huawei Digital Power Technologies Co., Ltd.