FusionPower6000
Maintenance Guide
●
Procedure
Step 1 Pull out the surge protection module.
Figure 6-20 Removing a surge protection module
Step 2 Install the new surge protection module.
----End
6.13 Replacing an SPD
Prerequisites
Do not replace an SPD during a thunderstorm.
●
●
Procedure
Step 1 Turn off the upstream switch for the SPD based on the electrical diagram and
labels.
Issue 02 (2022-07-18)
Material: a new and intact surge protection module of the same model
NO TE
If a surge protection module is damaged, it is recommended that all surge protection
modules be replaced.
D ANGER
Tools: electroprobe, insulated gloves, Phillips screwdriver, flat-head
screwdriver, step ladder
Material: a new and intact SPD of the same model
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Component Replacement
56