4.
Step 8 Install the new ECC800-Pro, and reinstall the cables, WiFi module, and antenna.
Step 9 Turn on the upstream switch for the cabinet.
Step 10 Choose Maintenance > Configuration File and import the backup configuration
file, or set parameters for the devices that connect to the ECC800-Pro to ensure
normal communication. Edit the plan view and add devices.
----End

6.5 Replacing a Smart ETH Gateway

Prerequisites
Procedure
Step 1 Mark the corresponding port names on the cables connected to the front and rear
of the smart ETH gateway, and then remove the cables.
Step 2 Remove the smart ETH gateway.
Figure 6-8 Removing a smart ETH gateway
Step 3 Install the new smart ETH gateway and reconnect the cables.
Step 4 On the ECC800-Pro WebUI, choose System Settings > Device Management >
Device Deletion and select a device type from the Select a device type drop-
down list. Select a desired device in the Devices list, click Delete, and add the new
device to the FusionPower6000 view. Edit the plan view and add devices. Choose
Monitoring > Smart ETH Gateway > Running Parameters and set Device name
for the new device to the device name before the replacement.
Issue 02 (2022-07-18)
Install the new ECC800-Pro main control module.
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, label, marker
Material: a new and intact smart ETH gateway of the same model
Copyright © Huawei Digital Power Technologies Co., Ltd.