7.2 Shutting Down and Powering Off a UPS

Context
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut
down; if the bypass is abnormal, the UPS supplies no power after the inverter is
shut down. Before shutting down the UPS, ensure that all loads have been shut
down.
Procedure
Step 1 Shut down the inverter.
If the inverter shuts down and the bypass is normal, the UPS transfers to bypass
mode. The Bypass mode alarm is displayed on the LCD.
Figure 7-1 Normal bypass
After you shut down the inverter, the UPS supplies no power if the bypass is
abnormal, which causes a power failure for the loads.
Issue 02 (2022-07-18)
NO TICE
Shutting down the inverter on the LCD
Choose Common Functions > Inv. OFF. After confirmation, the inverter is
shut down.
NO TE
You can also choose System Info > Maintenance > Inv. OFF to shut down the
inverter.
Shutting down the inverter on the WebUI
Choose Monitoring > UPS System > Running Control, and click Inv. OFF.