Powering On Loads - Huawei FusionPower6000 Maintenance Manual

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Maintenance Guide
Starting the Inverter on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 On the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End
Starting the Inverter on the WebUI
Step 1 Open a browser (Internet Explorer 11 as an example) and choose Tools > Internet
Options.
Step 2 Click the Advanced tab, check that Use TLS 1.2 and Use TLS 1.3 are selected, and
click OK.
Step 3 In the address box of the browser, enter https://
Step 4 Enter the correct user name and password and click Login.
Step 5 On the WebUI, choose Monitoring > UPS System > Running Control, and click
Inv. ON, and confirm the operation to start the inverter.
Figure 7-11 Starting the inverter
----End

7.7.2.6 Powering On Loads

Context
After the inverter starts, the UPS transfers to inverter mode, and the Bypass mode
alarm on the MDU disappears.
Issue 02 (2022-07-18)
NO TE
Change the password after your first login to prevent unauthorized access. You can choose
System Info > Settings > User Settings and change Password.
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.
NO TE
If the power module receives a startup command when it cannot be started, the startup
command will be retained for 1 minute. Within 1 minute, if there is no situation (for
example, the power module encounters other faults, executes a shutdown command, or a
fault is rectified) that requires the startup command to be cleared and the power module
becomes able to start, then the power module responds to the startup command.
Copyright © Huawei Digital Power Technologies Co., Ltd.
UPS IP address .
7 FAQ
85