Huawei FusionPower6000 Maintenance Manual page 58

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Maintenance Guide
Figure 6-13 Short-circuiting terminals (2)
Step 2 Mark the corresponding port names on the cables connected to the front and rear
of the centralized monitoring module, and then remove the cables.
Step 3 Remove the centralized monitoring module.
Figure 6-14 Removing the centralized monitoring module
Step 4 Install the new centralized monitoring module and reconnect the cables.
Step 5 If the centralized monitoring module in the cable inlet and bus tie cabinet
(combined or separated) or maintenance bypass cabinet is replaced, reinstall the
terminals of the current transformer based on the electrical diagram, labels, and
records.
Step 6 On the ECC800-Pro WebUI, choose System Settings > Device Management >
Device Deletion and select a device type from the Select a device type drop-
down list. Select a desired device in the Devices list, click Delete, and add the new
device to the FusionPower6000 view. Edit the plan view and add devices. Choose
Monitoring > Power Distribution > Running Parameters, set Device name for
the new device to the device name before the replacement, and set Device name
for the switch managed by the new device to the switch name before the
replacement.
Step 7 Check the parameters and communication status of the device to ensure normal
communication.
----End
Issue 02 (2022-07-18)
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Component Replacement
51