Huawei FusionPower6000 Maintenance Manual page 106

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Maintenance Guide
Step
Operation
Add Sensor
Setting AI/
DI_1 to the
compensati
on cabinet
SPD fault
signal
Plan View
Modifying
basic
configuratio
ns
Issue 02 (2022-07-18)
Parameter
Device Type
Connect To
Communicati
ons Port
Device
Address
AI/DI_1
sensor
AI/DI_1
sensor name
AI/DI_1
sensor type
Location
Layout
Half-size
cabinet
qty./row
Copyright © Huawei Digital Power Technologies Co., Ltd.
Setting
Select SVG-APF-NOVTIUM, SVG-In-
Power, or PDU-Sinexcel-svg100
from the drop-down list box.
● If the compensation modules are
from Novtium, select SVG-APF-
NOVTIUM.
● If the compensation modules are
from In-Power, select SVG-In-
Power.
● If the compensation modules are
from Sinexcel, select PDU-
Sinexcel-svg100.
Select System-Device name from the
drop-down list box.
Select COM3 from the drop-down list
box. In this example,
Communications Port is set to
COM3. During actual configuration,
set the communications port based
on the actual situation.
In this example, Device Address is
set to 1. During configuration, set the
actual device address.
Enable
Compensation cabinet SPD fault
Normal close
Indoor
Single-row
Calculate based on the
FusionPower6000 layout. A half-sized
cabinet is 300 mm wide. Round up
the value.