Mitsubishi Electric MELSEC iQ-R Series User Manual page 185

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
3160H
The number of points of link devices of the
device stations set to "CC-Link IE TSN
Class A" in "CC-Link IE TSN Class" of
"Network Configuration Settings" under
"Basic Settings" exceeds the number of
points that can be assigned.
31ACH
"CC-Link IE TSN Class Setting" of the
device station set in "Network
Configuration Settings" does not match "
CC-Link IE TSN Class Setting" in
"Connected Device Information" under
"Basic Settings".
3600H
• For the inter-module synchronization
cycle setting, the setting of the master
station does not match the inter-module
synchronization cycle setting of the local
station.
• "Fixed Scan Interval Setting" of "Inter-
module Synchronization Setting" in
"System Parameter" does not match
"Communication Period Interval Setting"
under "Communication Period Setting"
in "Basic Settings" of the module
parameter.
• The values out of communication cycle
setting range of the Motion module is
set in "Fixed Scan Interval Setting"
under "Inter-module Synchronization
Setting" in "System Parameter".
3601H
A mismatch occurs between the network
synchronous communication setting in the
network configuration settings of the
master station and the inter-module
synchronization target module selection of
the own station.
3602H
Inter-module synchronization cycle failure
occurred between networks.
3603H
The number of the slot on which a module
that cannot be set as the synchronization
master is mounted is set in "Mounting Slot
No." of the synchronization master in
"System Parameter".
3604H
A module to operate as an inter-module
synchronous master could not output an
inter-module synchronization signal.
Action
In "Network Configuration Settings" under "Basic Settings", review the
device assignment settings so that the number of points of link devices of the
stations with detailed information 2 does not exceed the number of points
assigned to stations with CC-Link IE TSN Class A.
Set "CC-Link IE TSN Class Setting" of the device station set in "Network
Configuration Settings" to "CC-Link IE TSN Class B". Or, set "CC-Link IE
TSN Class Setting" in "Connected Device Information" under "Basic
Settings" to "Mixture of CC-Link IE TSN Class B/A or CC-Link IE TSNClass
A Only".
• Correct the parameter so that all modules performing inter-module
synchronization have the same cycle setting.
• Check that the setting of "Fixed Scan Interval Setting" of "Inter-module
Synchronization Setting" in "System Parameter" is consistent with the one
of the communication cycle of the Motion module.
Change the parameter so that the setting of "Select Inter-module
Synchronization Target Module" under "Inter-module Synchronization
Setting" in "System Parameter" is the same as the setting of "Network
Synchronous Communication" under "Network Configuration Settings" in
"Basic Settings".
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• Check if the switching hub and the cables are connected properly.
• After taking the above action, power off and on or reset all the stations
where the error was detected.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Correct the setting of "Mounting Slot No." of the synchronization master in
"System Parameter".
• Check if the switching hub and the cables are connected properly.
• Power off and on or reset the own station.
• When this error is detected by more than one RJ71GN11-T2 (local station)
and RJ71GN11-EIP (local station), power off and on or reset each
RJ71GN11-T2 (local station) and RJ71GN11-EIP (local station) in the
order starting from the local station connected closest to the master
station.
Detailed
information 1
Detailed
information 2
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■Target station
information
• Station number
• IP address
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
■
■Parameter
information
• Parameter storage
location
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter storage
location
• Parameter type
• I/O No.
• Parameter No.
• Parameter item No.
■
■
■Synchronous master
setting information
• Synchronous master
mounted slot
number
4 TROUBLESHOOTING
183
4.5 List of Error Codes
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd78g4Rd78g8Rd78g16Rd78g32Rd78g64Rd78ghv ... Show all