Error
Error definition and causes
code
C056H
The read/write request exceeds the
largest address.
C057H
The request data length of the SLMP
message does not match the number of
data in the character (a part of text).
C058H
The request data length of the SLMP
message after the ASCII/binary
conversion does not match with the
number of data in the character (a part of
text).
C059H
• The specified command and
subcommand of the SLMP message are
incorrect
• A function that is not supported by the
target device was executed.
C05AH
The CC-Link IE TSN-equipped module
cannot read/write data from/to the device
specified by the SLMP message.
C05BH
The CC-Link IE TSN-equipped module
cannot read/write data from/to the device
specified by the SLMP message.
C05CH
The received request data of the SLMP
message is incorrect.
C05DH
The "Monitor Request" command is
received before the monitor registration is
performed by the "Monitor Registration/
Clear" command of the SLMP message.
C05EH
• The time between reception of the
SLMP request message by the CC-Link
IE TSN-equipped module and the
returned response from the access
destination exceeded the monitoring
timer value set in the command.
• An unresponsive command was sent to
another network station as the access
destination. (If this error does not cause
any problems, it can be ignored.)
C05FH
This request cannot be executed to the
access destination specified by the SLMP
message.
C060H
The request details for bit devices of the
SLMP message is incorrect.
C061H
• The request data length of the SLMP
message does not match the No. of
data in the character (a part of text).
• The write data length specified by the
label write command is not even byte.
C06FH
The network No. of request destination
specified by the SLMP request message is
not available for communications with the
station No.121 or later.
C070H
The device memory cannot be extended
for the access destination specified by the
SLMP message.
Action
• Correct the start address or the number of read/write points so that the
request does not exceed the largest address and send the data to the CC-
Link IE TSN-equipped module again.
• If the access target and connection stations are modules of the MELSEC
iQ-R series, send the SLMP message again to the CC-Link IE TSN-
equipped module using 003 and 002 of subcommands.
Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
• Check that there are no errors in the specification of the command and
subcommand of the SLMP message.
• Check whether the function executed is supported by the target device.
• Check the version of the target device.
Correct the specification of the device to be read/written and send the SLMP
message to the CC-Link IE TSN-equipped module again.
Correct the specification of the device to be read/written and send the SLMP
message to the CC-Link IE TSN-equipped module again.
Correct the request data and send the SLMP message to the CC-Link IE
TSN-equipped module again.
Register the monitoring data using "Monitor Registration/Clear" command
and perform monitoring.
• Increase the monitoring timer value.
• Check if the access destination is operating normally.
• Correct the network No. or request destination station No.
• If the access destination is a module with a different network No., correct
the routing parameter setting.
• If the access destination is a module with a different network No., check if
the network No. is not in use.
Correct the access destination.
Correct the request details and send the SLMP message to the CC-Link IE
TSN-equipped module again.
• Check and correct the text or request data length, and send the SLMP
message to the CC-Link IE TSN-equipped module again.
• Add one byte of dummy data, and specify the length as an even number of
bytes.
• If a 3E frame, 4E frame, or a station No. extension frame is used for the
SLMP, check that there is no error for the network No. of request
destination and station No.
• If a station No. extension frame is used for the SLMP, check that there is
no error for the network No. of the request destination and station No.
• Correct the SLMP message to read/write data without the device memory
set for extension.
• Specify the extension of the device memory only for an CC-Link IE TSN-
equipped module mounted station and a MELSEC iQ-R/Q/QnACPU via
CC-Link IE Controller Network, MELSECNET/H, or MELSECNET/10.
Detailed
information 1
Detailed
information 2
4 TROUBLESHOOTING
187
4.5 List of Error Codes