Error
Error definition and causes
code
3605H
A module to operate as an inter-module
synchronous master could not output an
inter-module synchronization signal.
3607H
The correction value of time counter
calculated by the inter-module
synchronization function exceeds
allowable range successively.
3608H
Inter-module synchronization signals have
not been input for a certain period of time.
3609H
An error has been detected in the inter-
module synchronization function.
360AH
An error has been detected in the inter-
module synchronization function.
360BH
An error has been detected in the inter-
module synchronization function.
360CH
An error has been detected in the inter-
module synchronization function.
360DH
• When multiple Motion modules are set
as the inter-module synchronization
targets, a Motion module with the
software version that cannot be set for
the inter-module synchronization master
is set.
• An error has been detected in the inter-
module synchronization function.
3C00H
A hardware failure has been detected.
3C01H
A hardware failure has been detected.
3C02H
A hardware failure has been detected.
4 TROUBLESHOOTING
184
4.5 List of Error Codes
Action
• Check the master station condition.
• Check the error of the master station and take action using the module
diagnostics of the engineering tool.
• Check that the settings of the master station are consistent with the one of
the device station in "Network Configuration Settings" under "Basic
Settings" of the master station.
• Check that the settings of the master station are consistent with the one of
the local station in "IP Address" under "Required Settings" of the local
station.
• Correct "IP Filter Settings" under "Application Settings".
• Check if the switching hub and the cables are connected properly.
• Power off and on or reset the own station.
• When this error is detected by more than one RJ71GN11-T2 (local station)
and RJ71GN11-EIP (local station), power off and on or reset each
RJ71GN11-T2 (local station) and RJ71GN11-EIP (local station) in the
order starting from the local station connected closest to the master
station.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Update the Add-on baseSystem version to "1.16" or later for the Motion
module set as the inter-module synchronization master.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module or base unit. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
Detailed
information 1
Detailed
information 2
■
■Synchronous master
setting information
• Synchronous master
mounted slot
number

Advertisement