Device station cyclic transmission information
■ CC-Link IE TSN Class A (low speed) multiple (Un\G1294304)
Stores the multiple n used to calculate the transmission delay time of a CC-Link IE TSN Class A device station for which
"Communication Period Setting" is set to "Low-Speed".
• 0: There is no device station on the network configuration with CC-Link IE TSN Class A and "Communication Period
Setting" set to "Low-Speed"
*1
• 1 or greater: n value
*1 When 'Protocol operating status' (Un\G1294016) is '1: Operating with the protocol version 1.0', it is set to 1 Fixed.
Own node setting status storage area
■ Own node IP address (Un\G2097156 to Un\G2097157)
The setting values of the IP address are stored.
Range: 1H to DFFFFFFEH
■ Subnet mask (Un\G2097166 to Un\G2097167)
The setting values of the subnet mask are stored.
Range: 1H to FFFFFFFFH
0: No setting
■ Default gateway IP address (Un\G2097170 to Un\G2097171)
The setting values of the default gateway are stored.
Range: 1H to DFFFFFFEH
0: No setting
■ Own node MAC address (Un\G2097180 to Un\G2097182)
The own node MAC addresses are stored.
• Un\G2097180: 5th byte, 6th byte of the MAC address
• Un\G2097181: 3rd byte, 4th byte of the MAC address
• Un\G2097182: 1st byte, 2nd byte of the MAC address
■ Own node network No. (Un\G2097183)
The setting value of the network No. is stored.
Range: 1 to 239
0: Network No. not set
■ Station No. (Un\G2097184)
The setting value of the station No. is stored.
Range: 1 to 120
0: Station No. not set
■ Transient transmission group No. (Un\G2097185)
The setting value of the transient transmission group No. is stored.
Range: 1 to 32
0: Group not specified
■ Auto-open UDP port port number (Un\G2097189)
The port number used for the auto-open UDP port is stored.
■ MELSOFT transmission port (TCP/IP) port number (Un\G2097190)
The port number used for the MELSOFT transmission port (TCP/IP) is stored.
■ MELSOFT transmission port (UDP/IP) port number (Un\G2097191)
The port number for the MELSOFT transmission port (UDP/IP) is stored.
■ SLMP transmission port (TCP/IP) port number (Un\G2097193)
The port number used for the SLMP transmission port (TCP/IP) is stored.
Appendix 1 Buffer Memory (When Using the PLCopen Motion Control FB Mode)