Appendix 3 List Of Link Special Relay (Sb) - Mitsubishi Electric MELSEC iQ-R Series User Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Appendix 3
The link special relay (SB) is turned on/off depending on various factors during data link. Any error status of the data link can
be checked by using or monitoring it in the program.
Application of link special relay (SB)
By using link special relay (SB), the status of CC-Link IE TSN can be checked from HMI (Human Machine Interfaces) as well
as the engineering tool.
Ranges turned on/off by users and by the system
The following ranges correspond to when the link special relay areas (SB) are assigned from SB0000 to SB0FFF.
• Turned on/off by users: SB0000 to SB001F
• Turned on/off by the system: SB0020 to SB0FFF
List of link special relay (SB)
The following table lists the link special relay areas (SB) when they are assigned from SB0000 to SB0FFF.
Do not turn on or off areas whose Nos. are not on the following list or ranges turned on/off by the system.
Doing so may cause malfunction of the programmable controller system.
: Available, : Not available
No.
Name
SB0006
Clear communication
error count
SB0014
Cyclic data receive
status clear
SB0016
Remote device
forced output request
SB0030
RECV execution
request flag CH1
SB0031
RECV execution
request flag CH2
SB0032
RECV execution
request flag CH3
SB0033
RECV execution
request flag CH4
SB0034
RECV execution
request flag CH5
SB0035
RECV execution
request flag CH6
SB0036
RECV execution
request flag CH7
List of Link Special Relay (SB)
Description
Clears the link special register areas (SW0074 to SW0077, SW007C to SW007F) related
to communication errors to 0.
OFF: Clear not requested
ON: Clear requested (valid while on)
Clears 'Cyclic data receive status' (SB0064).
While SB0014 is on, 'Cyclic data receive status' (SB0064) does not turn on.
OFF: Clear not requested
ON: Clear requested (enabled while on)
Requests to enable the remote device test function.
OFF: Not requested
ON: Requested
Stores the data reception status of own station channel 1.
OFF: No data received
ON: Data received
Stores the data reception status of own station channel 2.
OFF: No data received
ON: Data received
Stores the data reception status of own station channel 3.
OFF: No data received
ON: Data received
Stores the data reception status of own station channel 4.
OFF: No data received
ON: Data received
Stores the data reception status of own station channel 5.
OFF: No data received
ON: Data received
Stores the data reception status of own station channel 6.
OFF: No data received
ON: Data received
Stores the data reception status of own station channel 7.
OFF: No data received
ON: Data received
Availability
PLCopen
Motion
control FB
mode

Appendix 3 List of Link Special Relay (SB)

Simple
Motion
mode
A